Case: T05FR00303
Case Details
Entered Date:
03/01/2005
Applicant:
S & M ENTERPRISES LLC
Description:
Inspection
Outstanding Inspections
Case Number: T05FR00303
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 03/01/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 102.4- A Certificate of Occupancy is required and shall be posted in a conspicuous location. |
| 03/01/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.1- Storage of combustibles shall be maintained 2 feet or more below the ceiling of a non sprinklered building. (above cooler) |
| 03/01/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. 1. NE corner 2. N wall x 3 3. cash register 4. walk-in cooler |
| 03/01/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. NE corner 2. N wall 3. NW corner 4. microwave in kitchen |
| 03/01/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open junction boxes and open-wiring splices shall be prohibited. 1. E wall in bar area 2. receptacle cover plate behind bar 3. junction box to exposed wire to junction box 4. walk in cooler, several violations (pending electrical inspector) |
| 03/01/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers and fire sprinklers shall be maintained in operative conditions at all times. Fire extinguishers shall be serviced annually. 1. behind bar 2. kitchen x 2 3. fire suppression system in kitchen (change links) 4. hood system free of accumulated grease 5. 2 sprinkler heads in kitchen serviced or removed (not required) |
| 03/01/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1006.3- Illumination emergency power. In the event of a power failure, an emergency electrical system shall automatically illuminate exit access corridors. 1. dining area 2. game room |
| 03/01/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1011.2- Exit signs shall be internally or externally illuminated. (game room) |
| 03/01/2005 | VIOL - COMPRESSED GASES | JLANGEJA | Violation | TFC 3003.3- Compressed gas cylinders shall be secured to prevent accidental dislodgement. |