Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/01/2005

Applicant:

S & M ENTERPRISES LLC

Description:

Inspection

Outstanding Inspections

Case Number: T05FR00303
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
03/01/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 102.4- A Certificate of Occupancy is required and shall be posted in a conspicuous location.
03/01/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.1- Storage of combustibles shall be maintained 2 feet or more below the ceiling of a non sprinklered building. (above cooler)
03/01/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. 1. NE corner 2. N wall x 3 3. cash register 4. walk-in cooler
03/01/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. NE corner 2. N wall 3. NW corner 4. microwave in kitchen
03/01/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.6- Open junction boxes and open-wiring splices shall be prohibited. 1. E wall in bar area 2. receptacle cover plate behind bar 3. junction box to exposed wire to junction box 4. walk in cooler, several violations (pending electrical inspector)
03/01/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers and fire sprinklers shall be maintained in operative conditions at all times. Fire extinguishers shall be serviced annually. 1. behind bar 2. kitchen x 2 3. fire suppression system in kitchen (change links) 4. hood system free of accumulated grease 5. 2 sprinkler heads in kitchen serviced or removed (not required)
03/01/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1006.3- Illumination emergency power. In the event of a power failure, an emergency electrical system shall automatically illuminate exit access corridors. 1. dining area 2. game room
03/01/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1011.2- Exit signs shall be internally or externally illuminated. (game room)
03/01/2005 VIOL - COMPRESSED GASES JLANGEJA Violation TFC 3003.3- Compressed gas cylinders shall be secured to prevent accidental dislodgement.