Case: T05FR00298
Case Details
Entered Date:
03/01/2005
Applicant:
CHICANOS POR LA CAUSA INC
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00298
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/01/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.3 Combustibles shall not be stored in equipment rooms. |
03/01/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Fire alarm shall be in proper working order. System is in trouble mode. |
03/01/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.5 Emergency illumination lights shall be repaired. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00298
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/20/2005 | INSP - FULL | TKNAPP | Approved |