Case: T05FR00291
Case Details
Entered Date:
02/25/2005
Applicant:
MC DONALD S CORPORATION
Description:
full inspection
Outstanding Inspections
Case Number: T05FR00291
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| VIOL - BUILDING SVCS & SYSTEMS | None | Not Inspected | ||
| VIOL - FIRE RESIST.RATED CONST | None | Not Inspected | ||
| VIOL - FIRE PROTECTION SYSTEMS | None | Not Inspected | ||
| VIOL - MEANS OF EGRESS | None | Not Inspected | ||
| 02/25/2005 | INSP - FULL | FCONTRER | Correction Required | The hood system needs serviced TFC904.2.1 Extinguishers need service tagsTFC901.6 Exit blockedTFC1003.2.10.4,back door. Equipment up against electical panel. TFC605.3 Toaster cord damaged,need to replace.TFC605.5.3 Missing tile in basement need to replace.TFC 703.1 Basement emergency back-up light damaged, need to replace. TFC1003.2.8 |