Case: T05FR00267
Case Details
Entered Date:
02/22/2005
Applicant:
5151 E BROADWAY LLC
Description:
INSPECTION
Outstanding Inspections
Case Number: T05FR00267
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 17
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 1). Fire sprinkler test and inspection report shall be submitted to Tucson fire Department, all required repairs shall be completed. TFC 901.6 |
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 10). Suite 800: Currently poster is covering entire exit door. Door covering shall be removed from door. TFC 1027.4 |
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 11). Suite 800: Light fixture is hanging in grid to ceiling tiles. This light fixture shall be removed. TFC 703.3. |
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 12). Suite 320: Co2 extinguisher is on floor. CO2 extinguisher shall be mounted. TFC 901.6 |
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 13). Suite 320: New exit light shall be installed, current on has burned face. TFC 1011.5.2. |
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 14). Suite 250. Out of service extinguisher. Shall be removed TFC 901.6 |
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 15). Suite 140: Fire extinguisher shall be mounted at location discussed. TFC 901.6 |
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 16). Currently residential type deep fryer is being used. DSD inspector shall determine Hood and fire pretection requirements. This shall be referred to DSD. |
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 2). Fire pump operational test report shall be submitted to Tucson fire Department, all required repairs shall be completed. TFC 901.6 |
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 3). Fire alarm test inspection report shall be submitted to Tucson fire Department, all required repairs shall be completed. TFC 901.6 |
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 4). Fire drill shall be conducted. Date to be determined by 3-25-05. TFC 404.2. |
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 5). Currently doors with automatic door closures are being blocked open. This is against TFC 703.2.2, which states: 703.2.2 Hold-open devices and closers. Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position. All doors with door closures, unless with approved link, shall be kept closed. Currently doors in 1700,590,320 were found to be in violation of this code. |
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 5). Currently fire dept connection on above ground parking, is not labeled. This connection shall be labeled "Fire Department Connection". |
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 6). Currently several doors in stairs, do not fully close. All doors shall swing to a full closed position in leading into stairwells. As per TFC 703.2.3. 17th, 14th floor are some noticed. |
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 7). Suite 1400: exit light out of service. TFC 1011.5.2 |
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 8). Suite 1280: 28 inch exit width shall be provided between copy machine. |
02/22/2005 | INSP - FULL | EGRIFFIN | Violation | 9). On 10th floor, all combustible material shall be removed before removing ceiling tiles. No combustible material shall be allowed until ceiling tiles are in place. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00267
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/01/2005 | COMPL - REINSPECTION | EGRIFFIN | Approved | all violations approved |