Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/22/2005

Applicant:

5151 E BROADWAY LLC

Description:

INSPECTION

Outstanding Inspections

Case Number: T05FR00267
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 17
End Date Description Inspector Results Comments
02/22/2005 INSP - FULL EGRIFFIN Violation 1). Fire sprinkler test and inspection report shall be submitted to Tucson fire Department, all required repairs shall be completed. TFC 901.6
02/22/2005 INSP - FULL EGRIFFIN Violation 10). Suite 800: Currently poster is covering entire exit door. Door covering shall be removed from door. TFC 1027.4
02/22/2005 INSP - FULL EGRIFFIN Violation 11). Suite 800: Light fixture is hanging in grid to ceiling tiles. This light fixture shall be removed. TFC 703.3.
02/22/2005 INSP - FULL EGRIFFIN Violation 12). Suite 320: Co2 extinguisher is on floor. CO2 extinguisher shall be mounted. TFC 901.6
02/22/2005 INSP - FULL EGRIFFIN Violation 13). Suite 320: New exit light shall be installed, current on has burned face. TFC 1011.5.2.
02/22/2005 INSP - FULL EGRIFFIN Violation 14). Suite 250. Out of service extinguisher. Shall be removed TFC 901.6
02/22/2005 INSP - FULL EGRIFFIN Violation 15). Suite 140: Fire extinguisher shall be mounted at location discussed. TFC 901.6
02/22/2005 INSP - FULL EGRIFFIN Violation 16). Currently residential type deep fryer is being used. DSD inspector shall determine Hood and fire pretection requirements. This shall be referred to DSD.
02/22/2005 INSP - FULL EGRIFFIN Violation 2). Fire pump operational test report shall be submitted to Tucson fire Department, all required repairs shall be completed. TFC 901.6
02/22/2005 INSP - FULL EGRIFFIN Violation 3). Fire alarm test inspection report shall be submitted to Tucson fire Department, all required repairs shall be completed. TFC 901.6
02/22/2005 INSP - FULL EGRIFFIN Violation 4). Fire drill shall be conducted. Date to be determined by 3-25-05. TFC 404.2.
02/22/2005 INSP - FULL EGRIFFIN Violation 5). Currently doors with automatic door closures are being blocked open. This is against TFC 703.2.2, which states: 703.2.2 Hold-open devices and closers. Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position. All doors with door closures, unless with approved link, shall be kept closed. Currently doors in 1700,590,320 were found to be in violation of this code.
02/22/2005 INSP - FULL EGRIFFIN Violation 5). Currently fire dept connection on above ground parking, is not labeled. This connection shall be labeled "Fire Department Connection".
02/22/2005 INSP - FULL EGRIFFIN Violation 6). Currently several doors in stairs, do not fully close. All doors shall swing to a full closed position in leading into stairwells. As per TFC 703.2.3. 17th, 14th floor are some noticed.
02/22/2005 INSP - FULL EGRIFFIN Violation 7). Suite 1400: exit light out of service. TFC 1011.5.2
02/22/2005 INSP - FULL EGRIFFIN Violation 8). Suite 1280: 28 inch exit width shall be provided between copy machine.
02/22/2005 INSP - FULL EGRIFFIN Violation 9). On 10th floor, all combustible material shall be removed before removing ceiling tiles. No combustible material shall be allowed until ceiling tiles are in place.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00267
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/01/2005 COMPL - REINSPECTION EGRIFFIN Approved all violations approved