Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/17/2005

Applicant:

RGA PROPERTIES LLC

Description:

Inspection

Outstanding Inspections

Case Number: T05FR00260
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
02/17/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2- Storage of combustibles shall be orderly. Carts of clothing shall be arranged so that no more than 2 carts are together.
02/17/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.4- Multiplug adapters shall be prohibited. (front south wall)
02/17/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire protection systems shall be maintained and access shall be provided. A 36" minimum width shall be provided to sprinkler riser.
02/17/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.7- Fire extinguishers shall be installed on their hangers or brackets.
02/17/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1008.1.8.4- Manually operated flush bolts are not permitted. (east exit door)