Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/25/2005

Applicant:

CROCE VICTOR & ROSETTA CP/RS

Description:

Inspection

Outstanding Inspections

Case Number: T05FR00100
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
01/19/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.1- Storage of combustibles shall be a minimum of 2' from ceiling. (office)
01/19/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Abatement of electrical hazards. Wires are exposed in cooler. (outside)
01/19/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. under counters in front 2. pastry room x 2 (W,E) 3. fountain machine in front dining area 4. production room x 3 (S,W,ceiling) 5. office 6. patio awning
01/19/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.6- Open junction boxes shall be prohibited. (front counters x 4)
01/19/2005 VIOL - FIRE RESIST.RATED CONST JLANGEJA Violation TFC 703.1- Fire resistive rated construction shall be maintained. Ceiling tiles in pastry room shall be replaced.
01/19/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers shall be maintained on an annual basis, inspected, tested and maintained. 1. pastry room 2. production room x 2 (S,N)
01/19/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.7- Fire extinguishers shall be installed on their hanger or bracket. 1. pastry room 2. production room x 2 (S,N)
01/19/2005 VIOL - COMPRESSED GASES JLANGEJA Violation TFC 3003.3- Compressed gas cylinders shall be secured in an approved manner to prevent accidental dislodgement. (2 cylinders in pastry room)