Case: T05FR00074
Case Details
Entered Date:
01/19/2005
Applicant:
RIDDICK RONALD S & NATALIE G CP/RS
Description:
Inspection
Outstanding Inspections
Case Number: T05FR00074
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 01/18/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 102.3- A certificate of occupancy is required for change of ownership, change of use or any modifications done to the building. Contact Development Services at 791-5550. See handouts. |
| 01/18/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 102.4- Application of the building code. New structures shall comply with the International Building Code. Repairs, alterations and additions to existing structures shall comply with the IBC or the New Jersey Rehab Subcode. |
| 01/18/2005 | VIOL - FIRE SERVICE FEATURES | JLANGEJA | Violation | TFC 505.1- Address numbers shall be in accordance with Pima County address display requirements. See handout. |
| 01/18/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of not less than 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service panels. |
| 01/18/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. 1. main studio x 3 2. back room (nw) 3. kitchen |
| 01/18/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. main studio x 2 2. kitchen |
| 01/18/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire protection systems shall be maintained in operative conditions at all times. Fire extinguisher needs to be recharged. |
| 01/18/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.7- Hand-held portable fire extinguishers shall be installed on the hanger or bracket. |