Case: T05FR00048
Case Details
Entered Date:
01/13/2005
Applicant:
TERRAPIN TUCSON LLC
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00048
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 01/13/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.3 Equipment rooms - No storage in equipment rooms. Behind lobby front desk. Rooms at south building breezeway on first and second floors. Room at north side of north building. |
| 01/13/2005 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 505.1 Address numbers - Building shall have approved address numbers. |
| 01/13/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extinsion cord in the boiler room of housekeeping area shall not be used as permanent wiring. |
| 01/13/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Open junction box in the equipment room behind the front desk shall have an approved cover. |
| 01/13/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 Drywall shall be replaced on ceiling of equipment room located behind lobby front desk. |
| 01/13/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 The fire extinguisher in the laundry room shall be inspected. |
| 01/13/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 907.2.10 The smoke alarms in the housekeeping and maintenance areas shall be repaired. |
| 01/13/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit signs throughout the second floor shall be lit at all times. |
| 01/13/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.5 The emergency illumination lights in the main lobby at the north and south exits shall be repaired. |