Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

01/13/2005

Applicant:

TERRAPIN TUCSON LLC

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR00048
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
01/13/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.3 Equipment rooms - No storage in equipment rooms. Behind lobby front desk. Rooms at south building breezeway on first and second floors. Room at north side of north building.
01/13/2005 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 505.1 Address numbers - Building shall have approved address numbers.
01/13/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 Extinsion cord in the boiler room of housekeeping area shall not be used as permanent wiring.
01/13/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 Open junction box in the equipment room behind the front desk shall have an approved cover.
01/13/2005 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 Drywall shall be replaced on ceiling of equipment room located behind lobby front desk.
01/13/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 The fire extinguisher in the laundry room shall be inspected.
01/13/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 907.2.10 The smoke alarms in the housekeeping and maintenance areas shall be repaired.
01/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit signs throughout the second floor shall be lit at all times.
01/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.5 The emergency illumination lights in the main lobby at the north and south exits shall be repaired.