Case: T05FR00045
Case Details
Entered Date:
01/12/2005
Applicant:
LENT MICHAEL P 50% & QUICK JACK 50%
Description:
Inspection
Outstanding Inspections
Case Number: T05FR00045
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 01/12/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. 1. multiplug adapter on west wall (N) 2. multiplug adapter in front office (N wall) |
| 01/12/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be used as a substitute for permanent wiring. (front office) |
| 01/12/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open junction boxes shall be prohibited. 1. above sink 2. stock room ceiling 3. wash room ceiling |