Case: T05FR00008
Case Details
Entered Date:
01/05/2005
Applicant:
BASURTO ARMANDO
Description:
Inspection
Outstanding Inspections
Case Number: T05FR00008
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
01/05/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.1- Storage shall be maintained a minimum of 18" below sprinkler head deflectors. (bathroom) |
01/05/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (soda machine) |
01/05/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open junction boxes and open-wiring splices shall be prohibited. 1. all exterior light poles need cover plates. 2. open-wire splices on exterior alarm bell. |
01/05/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.4- Fire protection systems shall be extended as necessary to maintain protection whenever the building is altered, remodeled or added to. *Security closet needs sprinkler coverage. |
01/05/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6.1 Appendix C- Inspection and testing of sprinkler systems shall be conducted annually. Records shall be kept on premises and a copy shall be submitted to the Tucson Fire Dept. |
01/05/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1027.6- Where panic hardware or fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door. |
01/05/2005 | VIOL - COMPRESSED GASES | JLANGEJA | Violation | TFC 3003.3- Compressed gas cylinders shall be secured to prevent accidental dislodgement. (bathroom) |