Case Details

Status:

CANCEL

Type:

RES: MINIMUM HOUSING
Address:

Entered Date:

10/10/2005

Applicant:

WRIGHT EDNA

Description:

MULTIPLE EXTENSION CORDS GOING FROM METERBASE AND WATER HEATER TO OTHER UNITS AND GARAGE, PIGGYBACKING EXTENSION CORDS ACROSS UNITS.

Outstanding Inspections

Case Number: T05DV00880
Case Status: CANCEL
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
EMERGENCY CALL OUT None Not Inspected

Completed Inspections

Case Status: CANCEL
Case Number: T05DV00880
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 2
End Date Description Inspector Results Comments
10/10/2005 INSP - INITIAL CODE ENFORCMENT JORTA Approved RESPONDED TO A T.E.P CALL THAT THE SERVICE WAS BAD AND WIRES HANGING OUT. THE DISCREPNCIES FOUND AT THE SITE ARE AS FOLLOWS, BUT NOT LIMITED TO: THE UTILITY OWNED CONDUCTOR FROM THE GARAGE ARE APPROXIMATELY 20'' ABOVE THE ROOF. THE UTILITY COMPANY HAS A GREATER REQUIREMENT FOR THEIR SITUATION. HOWEVER THERE IS A/ IN THE JURISDICTION OF T.E.P THERE IS NO APPROVAL OF ANY INSPECTIONS FOR THE SERVICE UPGRADE, WIDENED BY THE USE OF SPLIT BOLT CONNECTORS TO TIE IN THE UTILITY CONDUCTOR AND THE PREMISES WIRING AT THE WEATHER HOOD AREA. THEIR CONNECTION IS ACCOMPLISHED BY A PERMANENT CRIMP TYPE OF CONNECTOR SYSTEM. THE INTER- CONNECTIONS ARE ALSO ILLEGAL IN THE FACT THAT THE DIRECT CONTACT OF THE ALUMINUM AND COPPER CONDUCTOR ARE IN DIRECT CONTACT WITH EACH OTHER, WHICH WILL CAUSE AN GALE-ANIX CORROSION OR ELECTROLISIS. THE SERVICE ALSO HAS A MULTITUDE OF VIOLATIONS SUCH AS IMPROPER COLOR CODE OF THE GROUNDED AND UNGROUDED CONDUCTOR SUCH AS USING THE WHITE CONDUCTOR AS A HOT CONDUCTOR. THE CIRCUIT BREACHER TERMINATIONS ARE DESIGNED FOR ONLY ONE CONDUCTOR AND THERE IS TWO CONDUCTORS UNDER THEIR TERMINATION AT SOME OF THE BREAKERS. A MAJOR CONCERN IN THE PLUMBING LINE THAT RUNS VERTICALLY A/ IN 6'' IN FRONT OF THE SERVICE PANEL BOARD. THIS SITUATION IS A SERIOUS SAFETY VIOLATION FOR ANY ONE WORKING IN THE PANEL. THERE WERE MANY MORE ELECTRICAL VIOLATIONS WHICH CAUSED ME TO HAVE THE UTILITY REMOVE THE METER AND DISALLOW ANY POWER TO REMAIN ON. OTHER ACTIVITIES THAT ARE TO BE INVESTIGATED IN THE ADDITION OF THE KITCHEN AT THE REAR OF THE MAIN HOUSE, WITH ELECTRICAL CIRCUITS, PLUMBING AND MODIFIED WALK AND STRUCTURAL COMPONENTS. ELECTRICAL CIRCUITS GOING OVERHEAD TO THE REAR HOUSE WERE ALL INSTALLED OVERHEAD USING NON METALIC SHEATHED CABLE AND APPROXIMATELY 8FT IN HEIGHT. THERE ARE MANY DISTINCTIONS OF THE REAR HOUSE WHICH DO NOT CONFIRM TO NORMAL TRADE PRACTICES WHICH TELL TALE NO PERMITS FOR THE REAR HOUSE, SUCH AS THE CIRCUITS ENTERING THROUGH THE EXTERIOR WALL IN EXPOSED ROMEX. THE ACTION TAKEN WAS TO CONDEM THE HOUSE UNDER THE ELECTRICAL VIOLATIONS THAT WERE FOUND. I DID TELL THE OWNERS SON ALFRED THAT A SERVICE UPGRADE WILL BE REQUIRED AND THAT THERE WILL BE FURTHER ITEMS THAT WILL HAVE TO BE VIEWED, SUCH AS THE REAR HOUSE AND THE ADDITION OF THE KITCHEN T.E.P WAS CALL TO DISCONNECT THE METER (METER NUMBER XH-223-374) OTHER POINTS OF IMPROPER ELECTRICAL ARE AS FOLLOWS: * IMPROPER OVERCURRENT PROTECTION * IMPROPER COLOR CODING * NO MAIN BREAKER * IMPROPER CLEARANCES IN FRONT OF THE SERVICE IE. WATER HEATER, PIPE AND CONCRETE * GROUNDING ELECTRODE CONDUCTOR LOOSE * UNPROTECTED EXPOSED ROMEX * IMPROPER TERMINATION OF ROMEX WIRING INTO BOX * DANGEROUS PENETRATION OF SINGLE CONDUCTOR THROUGH ZAGGED SHEET METAL OPENINGS. * LOOSE FITTINGS AND CONNECTIONS T.P.D WAS CALLED (APPROX 3PM) TO MONITOR ANYONE LIVING THERE WOULD BE ILLEGAL. NO ONE ALLOWED AFTER DARK. OK TO BE THERE IN DAYLIGHT FOR REPAIRS ONLY.
05/05/2006 INSP - FOLLOW UP CODE ENFORCE JORTA Approved MET W/ALFRED AS HE WAS LEAVING. I TOLD HIM THAT I WAS HERE ON A FOLLOW UP AND THAT I'LL BE TAKING SOME PHOTOS. ALFRED SAID THAT HE DID THE ELECTRICAL SERVICE UPGRADE AND THAT IT FINALLY PASSED. I TOLD ALFRED THAT THERE WERE OTHER ISSUES THAT I HAD NOTED TO HIM AND IF ANY THING HAD BEEN DONE? HE SAID YES, THE POWER TO GARAGE WAS DISCONNECTED AND THE POWER AND SERVICE RISER TO THE REAR HOUSE WAS DISCONNECTED AND REMOVED. I REITERATED THAT THE REAR HOUSE AND THE KITCHEN ADDITION (MY PERCEPTION) WERE NOT PERMITTED AND FURTHER RESEARCH WILL BE CONDUCTED. I ALSO NOTICED A NEW DUCT (2 1/2) INSTALLED AT FROM MAIN HSE TO REAR HSE.

Completed Activity Special Conditions

Case Description - RES: MINIMUM HOUSING
Case Number - T05DV00880
Case Status: CANCEL
Total Completed Case Activity Conditions: 1
Date Name
10/18/2005 NOTICE OF VIOLATION ISSUED

Documents

File Name Document Type  
2006-05-08 002.JPG IMAGES VIEW
2006-05-08 003.JPG IMAGES VIEW
2006-05-08 004.JPG IMAGES VIEW
2006-05-08 005.JPG IMAGES VIEW
2006-05-08 006.JPG IMAGES VIEW
2006-05-08 007.JPG IMAGES VIEW
2006-05-08 008.JPG IMAGES VIEW
2006-05-08 009.JPG IMAGES VIEW
2006-05-08 010.JPG IMAGES VIEW
2006-05-08 011.JPG IMAGES VIEW
2006-05-08 012.JPG IMAGES VIEW
2006-05-08 013.JPG IMAGES VIEW
2006-05-08 014.JPG IMAGES VIEW
2006-05-08 015.JPG IMAGES VIEW
2006-05-08 016.JPG IMAGES VIEW
2006-05-08 017.JPG IMAGES VIEW
2006-05-08 018.JPG IMAGES VIEW
2006-05-08 019.JPG IMAGES VIEW
2006-05-08 020.JPG IMAGES VIEW
2006-05-08 021.JPG IMAGES VIEW
2006-05-08 022.JPG IMAGES VIEW
2006-05-08 023.JPG IMAGES VIEW
2005-10-10 001 EAST 34TH ST..JPG None VIEW
2005-10-10 002 FRONT VIEW.JPG None VIEW
2005-10-10 003 SIDE VIEW.JPG None VIEW
2005-10-10 004 GARAGE AND OVERHEAD LINES.JPG None VIEW
2005-10-10 005 GARAGE VIEW.JPG None VIEW
2005-10-10 005 UTILITY LINES ABOVE GARAGE.JPG None VIEW
2005-10-10 006 INTERIOR GARAGE VIEW WITH NEW ROMEX None VIEW
2005-10-10 006 TEMP WIRING AT SERVICE DROP.JPG None VIEW
2005-10-10 007 REAR HOUSE WITH NEW HANGING ROMEX A None VIEW
2005-10-10 007 VIEW OF HAPHAZARDLY INSTALLED ROMEX None VIEW
2005-10-10 008 ANOTHER VIEW OF SERVICE UPGRADE.JPG None VIEW
2005-10-10 008 NEW WIRING, NEW PLUMBING.JPG None VIEW
2005-10-10 009 DANGEROUS WIRING TO HEATER, EXPOSED None VIEW
2005-10-10 009 ROMEX PENETRATION INTO REAR HOUSE.J None VIEW
2005-10-10 010 NEW WIRING INSTALLED, IMPROPER TERM None VIEW
2005-10-10 010 ROMEX RUN AND PENETRATION INTO REAR None VIEW
2005-10-10 011 LOOSE FITTINGS AND BOXES, IMPROPER None VIEW
2005-10-10 011 ROMEX CIRCUIT FROM SERVICE AREA.JPG None VIEW
2005-10-10 012 REAR HOUSE, WEST SIDE. SEE TRUSSES. None VIEW
2005-10-10 012 THIS STYLE OF ROMEX IS FRAYED.JPG None VIEW
2005-10-10 013 JUNK AND DEBRIS ALONG PROPERTY LINE None VIEW
2005-10-10 013 NOT EVEN ACCEPTABLE AS TEMP WIRING None VIEW
2005-10-10 014 NEWLY ADDED CIRCUITS.JPG None VIEW
2005-10-10 014 PLUMBING WASTE LINE AND COPPER LINE None VIEW
2005-10-10 015 COVER OF PANELBOARD DOES NOT SWING None VIEW
2005-10-10 015 VIEW FROM REAR HOUSE TO MAIN HOUSE. None VIEW
2005-10-10 016 PAN SHOT OF SERVICE. SEE EXTENSION None VIEW
2005-10-10 016 WEEDS AND VEHICLES AT BACK YARD.JPG None VIEW
2005-10-10 017 OLD CAMPER BODY.JPG None VIEW
2005-10-10 017 PENETRATION TO EXISTING CIRCUITS. E None VIEW
2005-10-10 018 NEW WATER HEATER .JPG None VIEW
2005-10-10 018 PENETRATION, DOUBLE LUGGING, IMPROP None VIEW
2005-10-10 019 ARC IN PANELBOARD.JPG None VIEW
2005-10-10 019 REAR HOUSE CIRCUITS BROUGHT IN FROM None VIEW
2005-10-10 020 2ND ARC IN PANELBOARD.JPG None VIEW
2005-10-10 020 ADDITION TO THE REAR HOUSE.JPG None VIEW
2005-10-10 021 BONDING CONTINUITY IMPAIRED AND UNA None VIEW
2005-10-10 021 FACIA AND OLD WEATHERHEAD.JPG None VIEW
2005-10-10 022 FRONT VIEW OF REAR HOUSE SERVICE.JP None VIEW
2005-10-10 022 HAPHAZARDLY INSTALLED WIRING AND SP None VIEW
2005-10-10 023 INTERMIXING OF DIFFERENT MANUFACTUR None VIEW
2005-10-10 023 REAR HOUSE, IMPROPER WIRING METHODS None VIEW
2005-10-10 024 NEW PLUMBING, WATER HEATER AND ADDI None VIEW
2005-10-10 024 PENETRATION VIEW.JPG None VIEW
2005-10-10 025 METER.JPG None VIEW
2005-10-10 025 WATER HEATER NOT WEATHER PROTECTED None VIEW
2005-10-10 026 REAR HOUSE VIEW FROM WEST.JPG None VIEW
2005-10-10 026 RECEPTACLE AND CORD TERMINATIONS.JP None VIEW
2005-10-10 027 GRASS AND DEBRIS ABOUT SERVICE.JPG None VIEW
2005-10-10 027 JUNK, DEBRIS AND AUTOMOBILE.JPG None VIEW
2005-10-10 028 ABOVE-GROUND WASTE LINE.JPG None VIEW
2005-10-10 028 EXTENSION CORD TO GARAGE.JPG None VIEW
2005-10-10 029 ABOVE-GROUND WASTELINE AT REAR HOUS None VIEW
2005-10-10 029 INCOMING AND OUTGOING LINES.JPG None VIEW
2005-10-10 030 MAIN HOUSE TO GARAGE AND TO REAR HO None VIEW
2005-10-10 030 REAR HOUSE WASTE LINE EXPOSED.JPG None VIEW
2005-10-10 031 CAR STORAGE IN REAR.JPG None VIEW
2005-10-10 031 GARAGE.JPG None VIEW
2005-10-10 032 EXTERIOR MAIN HOUSE, SHOWN IS ADDED None VIEW
2005-10-10 032 REAR WASTE LINE .JPG None VIEW
2005-10-10 033 IMPROPER, UNPERMITTED REAR WASTE LI None VIEW
2005-10-10 033 NEW CIRCUIT ENTRY INTO KITHCEN.JPG None VIEW
2005-10-10 034 REAR HOUSE ENTRY IN NEW ADDITION.JP None VIEW
2005-10-10 035 NORTH BOUNDARY FENCE.JPG None VIEW
2005-10-10 035 NORTH VIEW OF MAIN HOUSE KITCHEN.JP None VIEW
2005-10-10 036 ANOTHER VIEW OF JUNK AND DEBRIS.JPG None VIEW
2005-10-10 038 TRASH AND DEBRIS BY GARAGE, UNPAINT None VIEW
2005-10-10 038 YARD AREA.JPG None VIEW
2005-10-10 040 DRIVE.JPG None VIEW
2005-10-10 042 FRONT VIEW.JPG None VIEW
2005-10-10 043 FRONT SIDE VIEW.JPG None VIEW
2005-10-10 046 RIGHT FRONT.JPG None VIEW
2005-10-10 049 WEST WALL AT PROPERTY LINE.JPG None VIEW
2005-10-10 050 DANGEROUSLY INSTALLED FLOOD FIXTURE None VIEW
2005-10-10 051 BARE FIRE WAITING TO HAPPEN.JPG None VIEW
2005-10-10 052 NEW EXTENDED WALL AND BEARING.JPG None VIEW
2005-10-10 053 NEW PLUMBING.JPG None VIEW
2005-10-10 055 RUPTURED WIRE.JPG None VIEW
2005-10-10 056 FRAYED WIRE BROUGHT DOWN , IMPROPER None VIEW
2005-10-10 057 DOUBLE LUGGING AND WHITE AS UNGROUN None VIEW
2005-10-10 058 WEATHERED CIRCUIT BREAKERS.SAFETY M None VIEW
2005-10-10 062 GROUNDING ELECTRODE CONNECTION IMPA None VIEW
2005-10-10 063 WATER HEATER CABLE TERMINATION.JPG None VIEW
2005-10-10 064 BOTTOM PENETRATIONS HAS NO ROMEX CO None VIEW
2005-10-10 065 ANOTHER VIEW OF PANELBOARD PENETRAT None VIEW
2005-10-10 066 POSTED.JPG None VIEW
2005-10-12 001 SERVICE UPGRADE BEGUN, PANEL REMOVE None VIEW
2005-10-12 002 PANEL REMOVED LEAVING OLD WOOD AND None VIEW
2005-10-12 003 FAR SHOT OF SERVICE UPGRADE BEGUN.. None VIEW
2005-10-12 005 INTERIOR OF GARAGE WITH ROMEX REMOV None VIEW
2005-10-12 011 NEW ROMEX INSTALLED AT REAR HOUSE.J None VIEW
2005-10-12 014 DEBRIS AT PROPERTY LINE AND WASTELI None VIEW
2005-10-12 039 UPGRADE STARTED, OLD PANEL REMOVED. None VIEW
DOC1.PDF None VIEW
DOC2.PDF None VIEW