Case: T05DV00342
Case Details
Entered Date:
05/03/2005
Applicant:
SHORT CARL & ADRIENNE TR
Description:
COMPLAINT RE: MMIN HOUSING- LIVING CONDITIONS.
Completed Inspections
Case Status: COMPLIAN
Case Number: T05DV00342
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2005 | INSP - INITIAL CODE ENFORCMENT | HLOPEZ | Approved | MET DSD INSPECTOR LEERAY HANLEY, GLENN DEHORIA FIRE DEPT, BA ELECTRIC, IRA PIPER ON SITE. DSD INSP HANLEY INFORMED DNR INSPECTORS THAT ORIGINAL ACCESSMENT ON ELECTRICAL CONCERNS WITH ELECTRICAL PEDISTAL (LACK OF GROUNDING) WAS INCORRECT. ELECTRICAL FIRE WAS CAUSED BY BY-PASSING PEDISTAL PROTECTION AT SPACE 89. DNR INSPECTOR SPOKE WITH ELECTRICAL CONTRACTOR ON SITE. CONTRACTOR & INSP J. ORTA FROM DNR REVIEWED ELECTRICAL CONNECTION ON PEDESTAL & DETERMINED EACH PEDESTAL HAD SEPERATE GROUNDING HOWEVER MINOR ELECTRICAL VIOLATIONS WERE FOUND IN PEDISTAL, SUCH AS LACK OF BONDING IN SOME PEDISTALS, ALSO IMPROPER USE OF TWIST ON WIRE CONNECTORS WHICH ARE NOT COMPATABLE WITH LARGE WIRE SIZES INVOLVED. ELECTRICAL DISCONNECT SUPPORT SYSTEM WERE FOUND IN A DETERIORATED, DILAPIDATED STATE, 6X6 POLES HAS BEEN SEVERLY DAMAGED BY TERMITES & HAD TO BE SUPPORTED TEMPORALLY BY USE OF 2X4 LUMBER. 3/4 WOOD PANEL IS SPLITTING & FALLING APART. ON SITE ELECTRICAL CONTRACTOR HAS BEGUN MAINTENANCE REPAIR & SHOULD BE COMPLETED BY TOMORROW DNR INSP TO RETURN ON 5/4/05 TO CHECK COMPLETED REPAIRS. NOV WAS ISSUED TO PARK MANAGER VERONICA & WILL BE SENT TO OWNER. 30 DAYS WERE GIVEN & PICTURES WERE TAKEN. DSD POSTED UNIT & HAD PROPERTY AROUND STRUCTURE SECURED WITH CHAIN LINK FENCE PANELS BY FENCING CONTRACTOR. CONTACTED INSPECTOR II RICK SALDATE & GAVE BREAK DOWN OF EVENTS ALSO INFORMED HIM TRAILER PARK DOES HAVE ISSUE THAT COULD BE ADDRESS. INSP II INFORMED INSP H. LOPEZ THAT DUE TO LACK OF MAN POWER, OTHER ISSUES WILL NOT BE ADDRESSED AT THIS TIME. SPOKE WITH IVA AGAIN, STATED HIS COMPANY HAS BEEN ON SITE & STATED NO OTHER ELECTRICAL ISSUES WERE EXISTING AT THIS TIME. ISSUES SUCH AS WORK WITHOUT PERMITS ARE EVEDENT THROUGHOUT PARK. SOME TRASH & DEBRIS & DRIED VEGETATION. ATTACHED IS COPY OF PEDISTALS THAT WERE FOUND IN VIOLATION. |
| 04/17/2006 | EMERGENCY CALL OUT | HLOPEZ | Approved | REVIEWED CASE, ELECTRICAL VIOLATION HAS BEEN ABATED TO CODE, ATTACHED IS COPY OF ELECTRICAL GENERAL REPAIR T05EL01069 FINALED ON 6-15-2005. RESEARCHED IN PERMITS PLUS FOUND NO PERMITS ISSUED FOR HOT WATER TANK IN VIOLATION. NO ACTION HAD BEEN TAKEN ON THIS CASE DUE TO BEING MISSED PLACED IN RECORDS WILL SCHEDULE AN ONSITE FOLLOW UP INSPECTION FOR 5-15-06. |
| 05/15/2006 | INSP - FOLLOW UP CODE ENFORCE | HLOPEZ | Approved | VISITED SITE ON FOLLOW UP INSPECTION. NO ONE HOME. LEFT INFORMATION REGARDING NO ONE HOME. CASE TO BE ISSUED CITATION DUE TO UNABATED PLUMBING VIOLATION. EXISTING VIOLATION ON EXTERIOR, HOT WATER HEATER INSTALLED TO PROPANE APPEARS TO HAVE BEEN REMOVED, OTHER HOT WATER HEATER STILL LACKS REQUIRED TRP DRAIN VALVE AND FLUE VENT. HOT WATER HEATER LACKS TEMPERTURE CONTROL KNOB AND BURNER COMPARTMENT DOOR. WILL CHECK FOR PERMIT CITATION TO BE ISSUED FOR WORK WITHOUT PERMITS. PICTURES WERE TAKEN. REQUEST FORM POSTED ON FRONT DOOR AND INFORMING OWNER OF PENDING CITATION. CONTACT NUMBER ON FORM. |
Completed Activity Special Conditions
Case Description - RES: MINIMUM HOUSING
Case Number - T05DV00342
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 4
| Date | Name |
| 05/16/2005 | NOTICE OF VIOLATION ISSUED |
| 05/16/2005 | COURT ORDERED ABATEMENT |
| 07/01/2009 | VIOLATION CLOSED |
| 06/08/2006 | CITATION ISSUED |