Case: T04VL00795
Case Details
Entered Date:
12/01/2004
Applicant:
GRANT ROAD INDUSTRIAL LLC
Description:
COMPLAINT: EMER CALL OUT CFIR -
Outstanding Inspections
Case Number: T04VL00795
Case Status: COMPLIAN
Case Description: COM: FIRE
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| FOLLOW UP CODE VIOLATION | None | Not Inspected | ||
| 12/01/2004 | INITIAL CODE VIOLATION | LHANLY | Violation | 11/26/04 - 1" SPRINKLER PIPE BROKEN 24" FROM HEAD CAUSING FLOODING OF SPACE. SPRINKLERS SHUT OFF AT RISER. INSP OF ELECTRIC SYSTEM FOUND IT TO BE DRY AND PROPERLY FUNCTIONING. OWNER OF SPACE CONTACTED CUTLER FIRE SYSTEMS TO MAKE REPAIR AND PUT SPRINKLER SYSTEM BACK IN SERVICE. CULER AT SITE 7 PM AND WORK IN PROGRESS 9:30 PM SPRINKLER BACK IN SERVICE. NO FU REQUIRED. |