Case: T04FR00804
Case Details
Entered Date:
12/29/2004
Applicant:
SULLIVAN CHARLES F & JENNY L TR 45.622 &
Description:
Full Inspection
Outstanding Inspections
Case Number: T04FR00804
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/29/2004 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Ceiling clearance - Storage shall be maintained 18" below the level of the sprinkler heads. the storage level in the stockroom shall be lowered. |
12/29/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Inspection, testing and maintenance - The fire sprinkler system shall be tested annually. |
12/29/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit sign illumination - The exit signs at the main exit, the northeast exit, and at the east wall in the center shall be lit at all times and shall be repaired. |
12/29/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 Reliability - Required exit accesses shall be continuously maintained free from obstructions. the bed in front of the northeast exit shall be moved so as to provide 36 inches of aisle to the exit. |
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00804
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/12/2005 | INSP - FULL | TKNAPP | Approved |