Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/29/2004

Applicant:

SULLIVAN CHARLES F & JENNY L TR 45.622 &

Description:

Full Inspection

Outstanding Inspections

Case Number: T04FR00804
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
12/29/2004 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Ceiling clearance - Storage shall be maintained 18" below the level of the sprinkler heads. the storage level in the stockroom shall be lowered.
12/29/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 Inspection, testing and maintenance - The fire sprinkler system shall be tested annually.
12/29/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit sign illumination - The exit signs at the main exit, the northeast exit, and at the east wall in the center shall be lit at all times and shall be repaired.
12/29/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 Reliability - Required exit accesses shall be continuously maintained free from obstructions. the bed in front of the northeast exit shall be moved so as to provide 36 inches of aisle to the exit.

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00804
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/12/2005 INSP - FULL TKNAPP Approved