Case: T04FR00801
Case Details
Entered Date:
12/29/2004
Applicant:
R & S SHAH LLC
Description:
Full Inspection
Outstanding Inspections
Case Number: T04FR00801
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 15
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2004 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2 Storage in buildings - Storage of combustibles in buildings shall be orderly. Storage in the storage rooms south of the kitchen shall be orderly. |
| 12/29/2004 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.4 The area under the stairway in the maintenance room area shall not be used for storage of combustible materials. |
| 12/29/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Abatement of electrical hazards - The top cover of the clothes dryer shall be replaced in the housekeeping area to prevent electrical shock hazard. |
| 12/29/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 The ceiling light fixture in the maintenance room shall be repaired. |
| 12/29/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extension cords - The extinsion cord being used for the refrigerator on the north side of the kitchen shall not be used as permanent wiring and shall be removed. |
| 12/29/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction box in the ceiling in the housekeeping area above the dryers shall have an approved cover. |
| 12/29/2004 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 Holes in ceilings and walls shall be repaired. |
| 12/29/2004 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 Maintenance - The opening in the eaves at the outside north side of the building near the main exit shall be repaired to maintain the fire resistance rating. |
| 12/29/2004 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The hole in the ceiling in the hallway at the east side center exit shall be repaired. |
| 12/29/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Inspection - Portable fire extinguishers shall be inspected annually and mounted. |
| 12/29/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.3 Cleaning - The commercial cooking hood system shall be cleaned at intervals necessary to prevent the accumulation of grease. |
| 12/29/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.4 Extinguishing system service - The automatic fire extinguishing system for the cooking hood system in the kitchen shall be inspected every 6 months. |
| 12/29/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.7 The portable fire extinguisher in the maintenance room shall be mounted on a hanger. |
| 12/29/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 907.2.10 Smoke alarms - the single station smoke alarm located in the 2nd floor stairwell shall be required. The detector near room 111 shall be repaired. |
| 12/29/2004 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3 Security - The compressed gas cylinders in the kitchen area shall be secured to prevent them from falling. |
Completed Inspections
Case Status: FIELD
Case Number: T04FR00801
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2005 | INSP - FULL | TKNAPP | Approved |