Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/16/2004

Applicant:

TUCSON PLACE PARTNERS LLC

Description:

Full Inspection

Outstanding Inspections

Case Number: T04FR00781
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
12/16/2004 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 305.1 Clearance from ignition sources - Clearance shall be maintained between the water heater and combustibles.
12/16/2004 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Ceiling clearance - Storage shall be kept 18 inches below the level of the sprinkler heads.
12/16/2004 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 Working space and clearance - A clear space of 36 inches shall be maintained in front of electrical panels.
12/16/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 Inspection - The portable fire extinguishers shall be inspected annually.
12/16/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit sign illumination - The exit sign at the main exit south shall be lit at all times.

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00781
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/13/2005 INSP - FULL TKNAPP Approved