Case: T04FR00781
Case Details
Entered Date:
12/16/2004
Applicant:
TUCSON PLACE PARTNERS LLC
Description:
Full Inspection
Outstanding Inspections
Case Number: T04FR00781
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/16/2004 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 305.1 Clearance from ignition sources - Clearance shall be maintained between the water heater and combustibles. |
12/16/2004 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Ceiling clearance - Storage shall be kept 18 inches below the level of the sprinkler heads. |
12/16/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 Working space and clearance - A clear space of 36 inches shall be maintained in front of electrical panels. |
12/16/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Inspection - The portable fire extinguishers shall be inspected annually. |
12/16/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit sign illumination - The exit sign at the main exit south shall be lit at all times. |
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00781
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/13/2005 | INSP - FULL | TKNAPP | Approved |