Case: T04FR00773
Case Details
Entered Date:
12/15/2004
Applicant:
ROBERTS CHARLES P & BARBARA M TR 1/2
Description:
Inspection
Outstanding Inspections
Case Number: T04FR00773
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 12/15/2004 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of not less than 30" width, 36" depth, 78" height shall be provided in front of electrical service equipment. |
| 12/15/2004 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be used as a substitute for permanent wiring. (office) |
| 12/15/2004 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1008.1.8.3- Key locking hardware may be used on the main exit if there is a readily visible, durable sign on or above the door stating "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED". |