Case Number: T04FR00773
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
12/15/2004 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space of not less than 30" width, 36" depth, 78" height shall be provided in front of electrical service equipment.
12/15/2004 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be used as a substitute for permanent wiring. (office)
12/15/2004 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1008.1.8.3- Key locking hardware may be used on the main exit if there is a readily visible, durable sign on or above the door stating "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED".