Description:

Full Inspection

Outstanding Inspections

Case Number: T04FR00770
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
12/14/2004 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605 .3 Working space and clearance - A clear space of 36 inches in depth and 30 inches in width shall be maintained in front of the electrical service panels in the stockroom.
12/14/2004 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 Unapproved conditions - The open junction box and open wiring splices in the northwest side stockroom (light fixture) shall be repaired.
12/14/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 Inspection testing and maintenance - The portable fire extinguisher in the breakroom and on the sales floor shall be inspected and taged annually.
12/14/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 906.7 Hangers and brackets - The portable fire extinguisher in the breakroom shall be mounted on a hanger or bracket.
12/14/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 Reliability - The exit corridor on the west side of the building shall be continuously maintained free from obstructions. Storage shall be removed from the corridor.

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00770
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/28/2004 INSP - FULL TKNAPP Approved