Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/13/2004

Applicant:

TUCSON PLACE PARTNERS LLC

Description:

Full Inspection

Outstanding Inspections

Case Number: T04FR00763
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
12/13/2004 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 Working space and clearance - The electrical service equipment panels located in the stockroom shall have a clear space of 36 inches in depth and the width of the equipment.
12/13/2004 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 Maintenance - The hole in the north wall of the east side exit corridor shall be repaired.
12/13/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.4 Bolt locks - Manually operated flush bolts or surface bolts are not permitted. The flush bolt on the north exit near the stereo installation area shall be removed.
12/13/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.5 Illumination Emergency Power - The emergency lighting at the north side center exit shall be repaired.
12/13/2004 VIOL - LIQUID PETROLEUM GASES TKNAPP Correction Required 3803.2.1 Portable containers - The portable LP-Gas (Propane) containers located in the stockroom shall not be used in the building.

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00763
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/28/2004 INSP - FULL TKNAPP Approved