Case Number: T04FR00748
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
12/08/2004 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Ceiling clearance - Storage in food bar area shall be kept 18 inches below the level of the sprinkler heads.
12/08/2004 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 The electrical panels in the food bar area shall be provided with clear access.
12/08/2004 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 The missing ceiling tiles in the computer room and in the HVA stockroom shall be replaced.
12/08/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.6.4 Extinguishing system service - The hood system in the food bar shall be serviced every 6 months.
12/08/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The exit sign at the east side stockroom shall be repaired.

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00748
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/12/2005 INSP - FULL TKNAPP Approved