Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/08/2004

Applicant:

MC DONALDS REAL ESTATE COMPANY

Description:

Inspection

Outstanding Inspections

Case Number: T04FR00746
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
12/07/2004 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2- Storage shall be separated from heating devices. Water heater needs cover plate and combustibles removed.
12/07/2004 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.1- Storage shall be maintained 2 feet or more below ceiling in non-sprinklered buildings.
12/07/2004 VIOL - EMERGENCY PLAN/PREPARE JLANGEJA Violation TFC 405.2- Frequency of emergency evacuation plans shall be conducted every 3 months with employees.
12/07/2004 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 606.15- Electrical equipment in refrigeration rooms shall comply with the Int. Mechanical Code. Light cover needs to be replaced.
12/07/2004 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Maintenance of fire protection systems shall comply with NFPA standards. 1. Fire extinguishers need to be serviced annually. 2. Hood system is due for 6 month service.
12/07/2004 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 904.11.6.5- Fusible links shall be serviced annually. Show proof.
12/07/2004 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 10027.2- Panic hardware shall be maintained to be reliable and in working order. Test west gate on return.