Case Number: T04FR00737
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
12/07/2004 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2- Storage shall be separated from heating devices |
12/07/2004 | VIOL - EMERGENCY PLAN/PREPARE | JLANGEJA | Violation | TFC 405.2- Emergency evacuation drills shall be conducted with employees on a quarterly basis. Records shall be kept. |
12/07/2004 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of 30" width, 36" depth, 78" height shall be provided in front of electrical panels. |
12/07/2004 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.7- Hand held fire extinguishers shall be installed on hangers or brackets and in a conspicuous location. |
12/07/2004 | VIOL - COMPRESSED GASES | JLANGEJA | Violation | TFC 3003.3- Compressed gas cylinders shall be secured to prevent accidental dislodgement. |