Case Number: T04FR00730
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
12/03/2004 INSP - LIFE SAFETY TKNAPP Correction Required 904.11 Commercial Cooking Systems - The automatic fire extinguishing system for commercial cooking system shall be repaired, tested, and provide coverage for all cooking appliances.
12/03/2004 INSP - LIFE SAFETY TKNAPP Correction Required 904.11.5 A class K portable fire extinguisher shall be provided within 30 feet of commercial cooking equipment.