Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/02/2004

Applicant:

TUCSON PLACE PARTNERS LLC

Description:

Full Inspection

Outstanding Inspections

Case Number: T04FR00725
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
12/02/2004 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.3 The area of the electrical equipment panels and sprinkler riser shall be free from storage.
12/02/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6.1 A sprinkler head wrench shall be provided for head box.
12/02/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 903.3.3 Sprinklers shall not be obstructed, remove storage from top of "lockup cage" in stockroom.
12/02/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.3 A readily visible sign shall be posted at the front main exit stating This door to remain unlocked when building is occupied.
12/02/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit signs shall be lit at all times. Exit signs throughout shall be repaired.
12/02/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.3 The southeast door shall be free from obstructiions.

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00725
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/13/2005 INSP - FULL TKNAPP Approved