Case: T04FR00725
Case Details
Entered Date:
12/02/2004
Applicant:
TUCSON PLACE PARTNERS LLC
Description:
Full Inspection
Outstanding Inspections
Case Number: T04FR00725
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/02/2004 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.3 The area of the electrical equipment panels and sprinkler riser shall be free from storage. |
12/02/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6.1 A sprinkler head wrench shall be provided for head box. |
12/02/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 903.3.3 Sprinklers shall not be obstructed, remove storage from top of "lockup cage" in stockroom. |
12/02/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8.3 A readily visible sign shall be posted at the front main exit stating This door to remain unlocked when building is occupied. |
12/02/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit signs shall be lit at all times. Exit signs throughout shall be repaired. |
12/02/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.3 The southeast door shall be free from obstructiions. |
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00725
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/13/2005 | INSP - FULL | TKNAPP | Approved |