Case Details

Status:

PRECITE

Type:

INSPECTION
Address:

Entered Date:

12/02/2004

Applicant:

RASCON TIRSO & JULIETA

Description:

inspection

Outstanding Inspections

Case Number: T04FR00720
Case Status: PRECITE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
02/08/2005 INSP - REINSPECTION EGRIFFIN Violation This structure is approx., 990 square feet, in total. It regulates under TFC Section 24: Tents. This tent/structure is under requirements for regulation. The enclosure of this tent surrounds the structure on 4 sides. The plastic/fabric is an unknown material. On 12-1-04, it was requested that proof of flame retardant be supplied, to The Tucson Fire department. As of this time, no documents showing flame retardant has been shown or delivered. You are hereby ordered to show proof of flame retardant of enclosure material, or remove material, as per TFC 2404.2, TFC 2404.3, and TFC 2404.4.
12/02/2004 INSP - FULL EGRIFFIN Violation 1). Siding used is not authorized. Proof of flame retardant shell be furnished or plastic tarp shall be removed. TFC 2404.2 Flame retardant Label affixed will be certificate of approved material. TFC 2404.3 Label.

Completed Inspections

Case Status: PRECITE
Case Number: T04FR00720
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/25/2005 COMPL - REINSPECTION EGRIFFIN Approved on 2-25-05, plastic siding was removed.