Case: T04FR00714
Case Details
Entered Date:
12/01/2004
Applicant:
EXCEL REALTY TR INC
Description:
Full Inspection
Outstanding Inspections
Case Number: T04FR00714
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/01/2004 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The ceiling tiles in the computer room shall be repaired or replaced. |
12/01/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 The FDC shall be provided with a protective cap. |
12/01/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 903.3.3 Sprinklers shall not be obstructed by ceiling tiles. Sprinkler head in computer room. |
12/01/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8.3 A sign shall be posted on the east main exit stating This door to remain unlocked when building is occupied. |
12/01/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit sign at the east main exit door shall be lit at all times. |
12/01/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.5 The emergency lighting at the west exit shall be repaired. |
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00714
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/29/2004 | INSP - FULL | TKNAPP | Approved |