Description:

Full Inspection

Outstanding Inspections

Case Number: T04FR00714
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
12/01/2004 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 The ceiling tiles in the computer room shall be repaired or replaced.
12/01/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 The FDC shall be provided with a protective cap.
12/01/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 903.3.3 Sprinklers shall not be obstructed by ceiling tiles. Sprinkler head in computer room.
12/01/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.3 A sign shall be posted on the east main exit stating This door to remain unlocked when building is occupied.
12/01/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit sign at the east main exit door shall be lit at all times.
12/01/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.5 The emergency lighting at the west exit shall be repaired.

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00714
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/29/2004 INSP - FULL TKNAPP Approved