Outstanding Inspections

Case Number: T04FR00708
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
11/30/2004 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.4- Storage in attic and concealed spaces. Attics and concealed spaces used for storage of combustible materials shall be protected on the storage side as required for 1 hour fire resistive rated construction. (Equipment room)
11/30/2004 VIOL - EMERGENCY PLAN/PREPARE JLANGEJA Violation TFC 405.2- Frequency of emergency evacuation drills. Required emergency evacuation drills shall be held quarterly by all employees.
11/30/2004 VIOL - EMERGENCY PLAN/PREPARE JLANGEJA Violation TFC 405.4- Records. Records shall be maintained and the following information included: identity of person conducting drill, date and time of drill, notification method used, staff members on duty and participating, special conditions simulated, problems encountered, time required to accomplish evacuation.
11/30/2004 VIOL - FIRE RESIST.RATED CONST JLANGEJA Violation TFC 703.1- Maintenance. Required fire resistive rated construction shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Ceiling tiles need replacement in several areas. (Arena, Pro Shop, Stock room, Mop room)
11/30/2004 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.7- Hangers and brackets. Hand held portable fire extinguishers not housed in cabinets shall be installed on hangers or brackets. Please secure extinguishers in Office and Snack Bar areas.
11/30/2004 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1004.3- Posting of occupant load. Assembly occupancies shall have the occupant load posted in a conspicuous place, near the main exit. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner. *Contact Development Services @ 201 N Stone 791-5550*
11/30/2004 VIOL - COMPRESSED GASES JLANGEJA Violation TFC 3003.3- Security. Compressed gas cylinders shall be secured to prevent accidental dislodgement.
12/01/2004 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.6- Unapproved conditions. Open wiring splices shall be prohibited. (Arena lighting, above Sound booth)