Case: T04FR00702
Case Details
Entered Date:
12/01/2004
Applicant:
ARIZONA ACV VI LLC
Description:
Inspection
Outstanding Inspections
Case Number: T04FR00702
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
11/30/2004 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.1- Ceiling clearance. Storage shall be maintained a minimum of 18" below sprinkler head deflectors. Please lower stock in Pharmacy bathroom. |
11/30/2004 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.3- Equipment rooms. Combustible materials shall not be stored in mechanical rooms or electrical rooms. |
11/30/2004 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 606.1- Scope. Refrigeration systems shall be installed in accordance with the International Mechanical Code. The large amount of frost build up on the mechanical system is a concern and I have requested a Mechanical Inspector to look at it. |
11/30/2004 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | TFC 703.1- Maintenance . Fire resistive rated construction shall be maintained. Ceiling tiles need to be replaced, installed or adjustedto fill voids in Bakery. (x 2) |
11/30/2004 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Maintenance of fire protection systems. Extinguishing systems shall be maintained in operative conditions at all times. Fire extinguishers need to be serviced. 2 in Stock room, 1 in Floral, 1 in Meat |
11/30/2004 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.5.1- Markings. Individual containers shall be conspicuously marked or labeled in an approved manner. Please label 55 gallon drum in mechanical room. |
11/30/2004 | VIOL - COMPRESSED GASES | JLANGEJA | Violation | TFC 3003.3- Security. Compressed gas cylinders shall be secured to prevent accidental dislodgement. (Bakery x 2) |