Case: T04FR00682
Case Details
Entered Date:
11/23/2004
Applicant:
DETRICK SHELLEY B & BARBARA J
Description:
Full Inspection
Outstanding Inspections
Case Number: T04FR00682
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/23/2004 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 508.5.4 Obstructions - Fire protection equipment shall be free from obstructions. |
| 11/23/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 A working space of 30 x 36 x 78 inches shall be maintained in front of electrical equipment. |
| 11/23/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction box in the breakroom shall have an approved cover. |
| 11/23/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.7 Hangers - The fire extinguisher in the stockroom shall be mounted on a hanger. |
| 11/23/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.5 The emergency lighting in the office shall be repaired. |
| 11/23/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 Relibilty - Exit at northeast corner shall be free from obstructions. |
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00682
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2005 | INSP - FULL | TKNAPP | Approved |