Case: T04FR00657
Case Details
Entered Date:
11/18/2004
Applicant:
BAYVIEW ASSOCIATES
Description:
Full Inspection
Outstanding Inspections
Case Number: T04FR00657
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/18/2004 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage shall be kept 18 inches from sprinklers. |
11/18/2004 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.3 Combustibles shall not be stored in electrical equipment rooms. |
11/18/2004 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 508.5.4 Obstruction - Objects shall not be placed as to block FDC |
11/18/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3.1 The door to the electrical service room shall be labeled. |
11/18/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Covers shall be replaced on FDC. |
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00657
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/16/2004 | INSP - FULL | TKNAPP | Approved |