Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/18/2004

Applicant:

BAYVIEW ASSOCIATES

Description:

Full Inspection

Outstanding Inspections

Case Number: T04FR00657
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
11/18/2004 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage shall be kept 18 inches from sprinklers.
11/18/2004 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.3 Combustibles shall not be stored in electrical equipment rooms.
11/18/2004 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 508.5.4 Obstruction - Objects shall not be placed as to block FDC
11/18/2004 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3.1 The door to the electrical service room shall be labeled.
11/18/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 Covers shall be replaced on FDC.

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00657
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/16/2004 INSP - FULL TKNAPP Approved