Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/10/2004

Applicant:

DYBVIG DAVID 35% & LANGE DETLEF D &

Description:

Full Inspection

Outstanding Inspections

Case Number: T04FR00614
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
11/10/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 Extinguishers shall be inspected annually
11/10/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.5 A "K" class extinguisher shall be within 30 feet of cooking equipment
11/10/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.6.4 Hood system shall be serviced every 6 months
11/10/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.3 A visible sign stating This door to remain unlocked when building is occupied shall be posted near main exit
11/10/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.4 Flush bolts on north exit shall be removed
11/10/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit signs shall be illuminated at all times

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00614
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/08/2004 INSP - FULL TKNAPP Approved