Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/10/2004

Applicant:

LINDA VISTA VILLAGE LTD 84.8833%

Description:

Inspection

Outstanding Inspections

Case Number: T04FR00607
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
11/08/2004 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.1- Ceiling clearance. Storage shall be maintained a minimum of 18" below sprinkler head deflectors. Please lower storage of combustibles in closet.
11/08/2004 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.4- Multiplug adapters. Unfused multiplug adapters shall be prohibited. Devices must comply with ICC Electrical Code. 1. cube adapter behind soda fountain. 2. cube adapter by cash register.
11/08/2004 VIOL - FIRE RESIST.RATED CONST JLANGEJA Violation TFC 703.1- Maintenance. Fire resistive rated construction shall be maintained. Please replace/install missing ceiling tiles in storage closet.
11/08/2004 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1008.1.8.3- Locks and latches. A readily visible durable sign shall be posted above the door stating "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED". Letters shall be 1" high on contrasting background.
11/08/2004 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1011.2- Illumination. Exit signs shall be internally or externally illuminated. Exit sign is not functioning properly.