Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/09/2004

Applicant:

CNL INCOME FUND XII LTD

Description:

Full Inspection

Outstanding Inspections

Case Number: T04FR00600
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
11/09/2004 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 Blanks shall be provided in place of missing breakers in the electrical panel in the kitchen.
11/09/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.5 A "K" class extinguisher shall be provided within 30 feet of cooking equipment.
11/09/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit signs shall be illuminated at all times. Signs in dining area and in kitchen shall be repaired.
11/09/2004 VIOL - COMPRESSED GASES TKNAPP Correction Required 3003.3 Compressed gas cylinders shall be secured from falling.

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00600
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/23/2004 INSP - FULL TKNAPP Approved