Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/01/2004

Applicant:

DUCA DENNIS TRUST OCT 21, 1992 50%

Description:

Inspection

Outstanding Inspections

Case Number: T04FR00500
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
10/19/2004 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.1- Storage shall be at least 18" below sprinkler head.
10/19/2004 VIOL - EMERGENCY PLAN/PREPARE JLANGEJA Violation TFC 407.2- MSDS for all haz mats shall be readily available on premises.
10/19/2004 VIOL - EMERGENCY PLAN/PREPARE JLANGEJA Violation TFC 407.4- Persons in area where haz mats are stored, dispensed, handled or used shall be trained on how to use MSDS.
10/19/2004 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space of 30" x 36" x 78" shall be provided in front of electrical panels.
10/19/2004 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.6- The path of egress shall not be interrupted and obstructions shall not be placed in the required width of the exit.