Case: T04FR00477
Case Details
Entered Date:
10/22/2004
Applicant:
LAS MARGARITAS INC
Description:
Full Inspection
Outstanding Inspections
Case Number: T04FR00477
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/22/2004 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 505.1 Existing buildings shall have approved address numbers posted. |
10/22/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 The light in the freezeer shall be fixed. |
10/22/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11 The mesh type filters shall be replaced with baffel type on hood system. |
10/22/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.5 A class K extinguisher shall be provided 30 feet from the cooking equipment. |
10/22/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.4 The commercial hood system shall be inspected. |
10/22/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8.3 The two north exit doors shall have a sign stating This door to remain unlocked when building is occupied. |
10/22/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8.4 The bolt locks on the est doors and the south door shall be removed. |
10/22/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1011.1 Exit signs shall be posted at two north exit doors and at west end of south east dining room. Exit signs shall be illuminated. |
10/22/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 The emergency lighting at the bar and in the kitchen shall be repaired. |
10/22/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.5 Emergency lighting shall be provided for the two south dining areas. |
10/22/2004 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3 Compressed gas bottles shall be secured. |
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00477
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/15/2004 | INSP - FULL | TKNAPP | Approved |