Case: T04FR00454
Case Details
Entered Date:
10/15/2004
Applicant:
DND NEFFSON CO
Description:
Full Inspection
Outstanding Inspections
Case Number: T04FR00454
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/15/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3.1 Labeling - Door into electrical control panel room shall have a sign stating Electrical Room. |
| 10/15/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Unapproved conditions - Approved covers shall be provided for open junction boxes in freezer and in electrical room. |
| 10/15/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 912.5 Maintenance - FDC on north side shall have protective caps secured. |
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00454
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2004 | INSP - FULL | TKNAPP | Approved |