Case: T04FR00445
Case Details
Entered Date:
10/07/2004
Applicant:
ARIZONA EQUITIES INVESTOR GROUP LP
Description:
Full Inspection
Outstanding Inspections
Case Number: T04FR00445
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 14
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/07/2004 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 504.2 The southeast rollup door must have a sign stating this door blocked. |
10/07/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Junction box shall have cover. |
10/07/2004 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The doorway joining the two offices through the fire resistance rated assembly (wall) shall be protected with a self closing door. |
10/07/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.3 A 2A fire extinguisher shall be located in the office area. |
10/07/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.7 All fire extinguishers shall be mounted on hangers. |
10/07/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8.4 Manually operated flush bolts shall be removed. |
10/07/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 The southeast door shall be kept free from obstructions. |
10/07/2004 | VIOL - WELDING & OTHER HOT WRK | TKNAPP | Correction Required | 2604.2.6 - A 2A:20BC extinguisher shall be located in each manufacturing area. |
10/07/2004 | VIOL - HAZARDOUS MATERIALS,GEN | TKNAPP | Correction Required | 2701.5.2 A HMIS shall be kept on the property. |
10/07/2004 | VIOL - HAZARDOUS MATERIALS,GEN | TKNAPP | Correction Required | 2703.5.1 Rooms containing compressed gas shall be labeled compressed gas. |
10/07/2004 | VIOL - HAZARDOUS MATERIALS,GEN | TKNAPP | Correction Required | 2703.7.1 No smoking signs shall be posted. |
10/07/2004 | VIOL - HAZARDOUS MATERIALS,GEN | TKNAPP | Correction Required | 2703.8.7 Flamable liquids shall be stored in a liquid storage cabinet. |
10/07/2004 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3203.4.1 NFPA 704 sign shall be posted |
10/07/2004 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3203.4.2 Containers shall be marked with name of gas contained. |
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00445
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/05/2005 | INSP - FULL | TKNAPP | Approved |