Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

10/06/2004

Applicant:

MAGNA INVESTMENT & DEVELOPMENT CORP

Description:

Full Inspection

Outstanding Inspections

Case Number: T04FR00442
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
10/06/2004 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Ceiling clearance - Storage throughout the building shall be kept a minimum of 18" below sprinkler heads.
10/06/2004 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 Maintenance - Ceiling tiles throughout the building shall be replaced when damaged or missing.
10/06/2004 VIOL - FLAMMABLE LIQUIDS TKNAPP Correction Required 3404.3.4.4 Combustible liquids shall be stored in a liquid storage cabinet.

Completed Inspections

Case Status: FIELD
Case Number: T04FR00442
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/12/2004 INSP - FULL TKNAPP Approved