Case: T04FR00437
Case Details
Entered Date:
10/05/2004
Applicant:
MAGNA INVESTMENT & DEVELOPMENT CORP
Description:
Inspection
Outstanding Inspections
Case Number: T04FR00437
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2004 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 304.1 Waste accumlation prohibited - Combustible waste shall not be allowed to accumulate on third floor. |
10/05/2004 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2 Storage in buildings - Storage of combustibles in buildings shall be orderly. Storage throughout third floor shall be maintained to keep aisles open. |
10/05/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.7 Hangers and brackets - Hand held portable fire extinguishers shall be installed on hangers. |
10/05/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit sign illumination - Exit signs throughout the third floor shall be illuminated. |
10/05/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.5 Illumination emergency power - Emergency egress illumination shall be provided throughout the third floor. Emergency lights shall be repaired. |
10/05/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 Reliability - Exit accesses throughout the third floor shall be continuously maintained free from obstructions. |
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00437
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/12/2004 | INSP - FULL | TKNAPP | Approved |