Description:

Full Inspection

Outstanding Inspections

Case Number: T04FR00421
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
09/30/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 912.2.2 Existing buildings - Post FDC sign so it can be seen from the road.
09/30/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1503.2.6 Smoking Prohibited - No smoking signs shall be posted.
09/30/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.6 Fire protection - Spray booth shall be protected by a fire extinguishing system. Valve shall be secured in the OPEN position.
09/30/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.6.4 Fire extinguishers - A portable fire extinguisher rated 4A 40B shall be within 30 feet of spray booth.
09/30/2004 VIOL - HAZARDOUS MATERIALS,GEN TKNAPP Correction Required 2703.5 Hazard Identification signs - Visible hazard identification signs shall be posted at the entrance to building where hazardous materials are stored.
09/30/2004 VIOL - FLAMMABLE LIQUIDS TKNAPP Correction Required 3404.3.4.4 Flammable liquids shall be stored in a liquid storage cabinet.

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00421
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/03/2004 INSP - FULL TKNAPP Approved