Case: T04FR00414
Case Details
Entered Date:
09/29/2004
Applicant:
HIGH POINT ASSOCIATES & HECHT MILTON TR
Description:
Full Inspection
Outstanding Inspections
Case Number: T04FR00414
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2004 | VIOL - EMERGENCY PLAN/PREPARE | TKNAPP | Correction Required | 406.3.3 Fire safety training - Employees shall be aware of the location and operation of the manual pull station for the hood extinguishing system. |
| 09/29/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Abatement of electrical hazards - Exit sign at northeast corner exit is hanging by its wires and shall be repaired. |
| 09/29/2004 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 Maintenance - Cieling and wall in electrical room shall be repaired. |
| 09/29/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Inspection, testing, and maintenance - K class extinguisher in kitchen area shall be inspected and tagged. |
| 09/29/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1004.3 Posting of occupant load - Assembly occupancies shall have the occupant load posted. |
| 09/29/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8.4 Bolt locks - Manually operated flush bolt on rear exit shall be removed. |
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00414
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2004 | INSP - FULL | TKNAPP | Approved |