Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/28/2004

Applicant:

SANTOS DANIEL JR & CAROL J CO-TRUSTEES

Description:

Inspection

Outstanding Inspections

Case Number: T04FR00410
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
09/28/2004 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Abatement of electrical hazards. Circuit breakers shall not be secured in any manner. Remove tape.
09/28/2004 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords. Ext. cords shall not be a substitute for permanent wiring. Remove and use approved appliance. 1. front office x 2 2. ext. cord to fish tank 3. ext. cord running thru ceiling in back room 4. ext. cord on west wall
09/28/2004 VIOL - FIRE RESIST.RATED CONST JLANGEJA Violation TFC 703.1- Fire rated construction. Fire resistive rated construction shall be maintained. Ceiling tile in fan room needs to be fixed.
09/28/2004 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.1- Portable fire extinguishers. Where required, portable fire extinguishers shall be installed. You are required to have 1 2A fire ext. see handout for mounting req's.