Case: T04FR00394
Case Details
Entered Date:
09/24/2004
Applicant:
VALENCIA I-19 INVESTMENTS LLC
Description:
Applied for new C of O
Outstanding Inspections
Case Number: T04FR00394
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2004 | VIOL - FIRE PROTECTION SYSTEMS | CSCHULTZ | Violation | TFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. 1. Shall correct fire sprinkler system coverage in back storage and employee break room. 2. Shall have a complete sprinkler inspection done and have all areas instecped for proper coverage. |
| 09/23/2004 | VIOL - MEANS OF EGRESS | CSCHULTZ | Violation | 1003.3.1.8 Locks and latches. Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1. Shall remove all cross bars on all exit doors, at no time can you use an unapproved locking device. Panic hardware is on the doors and that is the only approved locking device allowed. |
| 11/01/2004 | INSP - FULL | CSCHULTZ | Violation | TFC 110 Unsafe Building. & 110.1.1 unsafe conditions. Field notice given ordering no merchandise to be stored in rear stock room until sprinkler system is repaired. This room is to stay clean until repairs are made. Also I talked to Art Mathieson from building safety and he had no problems with merchandise being installed, but does not want business to open to the public until roofing tile on porch is reapir. Reinspection will be made by myself and Art Mathieson building safety inspector when all work is done. |