Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/16/2004

Applicant:

SANTOS DANIEL JR & CAROL J TR

Description:

Full Inspection

Outstanding Inspections

Case Number: T04FR00379
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
VIOL - BUILDING SVCS & SYSTEMS None Not Inspected
09/16/2004 INSP - FULL JLANGEJA Violation TFC 605.1- Abatement of electrical hazards. 1. curcuit panel needs approved cover to prevent shock hazard. 2. locks on circuit breakers need to be removed. (x3)
09/16/2004 INSP - FULL JLANGEJA Violation TFC 605.4- Multi-plug adapters. Unfused adapters shall be prohibited. 1. gang plug on SE wall. 2. gang plug on E wall near ceiling.
09/16/2004 VIOL - FIRE RESIST.RATED CONST JLANGEJA Violation TFC 703.1- Fire resistive rated construction. Fire resistive construction shall be maintained. 1. ceiling tile in kitchen. 2. ceiling tile above walk in cooler. 3. ceiling tile in office. 4. ceiling tile in dining room.
09/16/2004 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC904.11.5- Commercial cooking equipment. Cooking equipment involving vegetable or animal fats and oils shall be protected by a class K portable fire extinguisher.
09/16/2004 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.2.11- Means of egress illumination. Emergency power shall be provided to exits and emergency lights.