Case: T04FR00370
Case Details
Entered Date:
09/14/2004
Applicant:
MC CUISTION ELIZABETH TR
Description:
Fire Inspection
Outstanding Inspections
Case Number: T04FR00370
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2004 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 505.1 Address numbers - Buildings shall have approved address numbers visible from the street. Buildings <50 feet from the curb require 12" numbers. |
| 09/14/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.5 Commercial cooking equipment - Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. A Class K extinguisher shall be used to provide protection for cooking equipment. |
| 09/14/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit sign illumination - Exit signs shall be illuminated at all times. Exit sign in kitchen leading to rear exit shall be repaired. |
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00370
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2004 | INSP - FULL | TKNAPP | Approved |