Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/27/2004

Applicant:

BREWSTER CENTER DOMESTIC VIOLENC

Description:

Full 3 year cycle

Outstanding Inspections

Case Number: T04FR00329
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
08/27/2004 INSP - FULL SHIGGINB Violation
08/27/2004 VIOL - FIRE SERVICE FEATURES SHIGGINB Violation TFC 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers, or approved building identification placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). 1. Must have approved address signage.
08/27/2004 VIOL - FIRE PROTECTION SYSTEMS SHIGGINB Violation TFC 903.2.9 Group R-4. An automatic sprinkler system shall be provided throughout all buildings with a Group R-4 fire area with more than eight occupants. Note: Occupancy is in the process of of remodling and sprinkler will be address with permiting and a Cof O with city of tucson
08/27/2004 VIOL - MEANS OF EGRESS SHIGGINB Violation TFC