Case: T04FR00323
Case Details
Entered Date:
08/24/2004
Applicant:
HOPP JACK
Description:
Fire Inspection
Outstanding Inspections
Case Number: T04FR00323
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.4 Multiplug adapter - Multiplug adapters shall not be used. |
| 08/24/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Unapproved conditions - Open wiring splices in freezer shall be repaired. |
| 08/24/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 609.7 Makeup air - Makeup air shall be supplied when operating kitchen hood system. |
| 08/24/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | Abatement of electrical hazards - Electrical wiring that is damaged shall not be used. Wiring to hood system blower motor on roof shall be repaired. |
| 08/24/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | Extension cords - Extension cords shall not be used as permanent wiring. Cords shall not be extended through cieling. |
| 08/24/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.5 - Comercial Cooking equipment - Cooking equipment shall be protected by class K portable fire extinguisher. Extinguisher shall be located within 30 feet of hood system. |
| 08/24/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.3 - Cleaning - Kitchen Hood system shall be cleaned to prevent the accumulation of grease. |
| 08/24/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1003.3.1.8 Locks and Latches - Egress doors shall be readily openable from the egress side without the use of a key. The front main exit on the east side shall have a sign stating "This door to remain unlocked when building is occupied" |
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00323
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2004 | INSP - FULL | TKNAPP | Approved |