Case: T04FR00315
Case Details
Entered Date:
08/19/2004
Applicant:
KLETECHKA LADDIE V & HANA J
Description:
Fire Inspection
Outstanding Inspections
Case Number: T04FR00315
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/19/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | Abatement of electrical hazards - Power cord from sign at northeast corner of building shall be removed from exit sign. |
| 08/19/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11 - Comercial cooking systems - Cooking hood system coverage shall be maintained. |
| 08/19/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.6.1 - System test - Hood system shall be inspected and tested for proper operation at 6 month intervals. |
| 08/19/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1003.3.1.8 Locks and Latches - A readily visible sign shall be posted above door stating "This door to remain unlocked when building is occupied". |
| 08/19/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1010.3 Exit sign illumination - Exit signs throughout building shall be illuminated at all times. |
| 08/19/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | Means of egress illumination - The means of egress shall be illuminated at all times. Emergency lighting in kitchen shall be repaired. |
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00315
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2004 | INSP - FULL | TKNAPP | Approved |