Fire Inspection

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00194
Case Description: INSPECTION
Total Completed Inspections - 4
End Date Description Inspector Results Comments
07/19/2004 VIOL - AEROSOLS TKNAPP Approved 2806.4 Aerosol containers shall not be stacked more than 6' high. Relocate containers in north storeroom.
07/19/2004 VIOL - MEANS OF EGRESS TKNAPP Approved 605.3 Working space of 30" by 36" must be maintained around electrical panel. Extinsion cords are not suitable for permanent wiring. Remove cord a front enterance.
07/19/2004 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Approved 1010.5 Emergency lights not working in north and south storeroom 1003.2.8 Gates prevent egress continuity. Remove locks. 1003.3.1.8 Remove locks from gates in rear of building.
08/05/2004 INSP - FULL TKNAPP Approved